Producdt Description:
ZCPE-pilot operated breather valve with flame arrester is a bit different with breather valve ,first let the seat leakage closer to set point ,second full flow without overpresure ,to maintain the tank pressure balance, reduce safety energy-saving products medium volatile, but also the use of principles of vapor heat transfer, protect the respiratory valve parts is not easy to freeze, the breathing valve to ensure the normal work, equipped with fire retardant explosion-proof function.
Fire breathing valve produced by our company has simplified structure, ventilation volume, less leakage, corrosion resistance, insulationetc.. The valve adopts polytetrafluoroethylene material, has the advantages of low temperature resistant, anti frost. The electrostaticprotection device is provided with a respiratory valve, the valve and the tank to keep the same potential moment.
Operating pressure:
| Type A: | +355pa(+36mmH2O) -295pa(-30mmH2O) |
| Type B: | +980pa(+100mmH2O)-295pa(-30mmH2O) |
| Type C: | +1950pa(+200mmH2O) -295pa(-30mmH2O) |
| Type D: | according to user requirement (special pressure rating) |
| Material: | WCB SS304 SS304L SS316 SS316L |
| Flange Standard: | HG/T20592-2009 ANSI B16.5 HG/T 20615-2009(Class series) HG/T20592-2009 (PN series) ANSI B16.5 AMSE B16.5 |
Note:
Under normal circumstances, (fire) breathing valve operating pressure to B shall prevail;
Applicable materials: gasoline, kerosene, diesel, aromatics, sulfur, air and other petrochemical materials;
Environment temperature: -40 °C -+60 °C;
Shell material: HT, AL, A3, 18-8, 304, 304L, 316, 316L.
Flange standards: HG20592-97 PN1.0 (also can be produced according to user specified criteria)
“Ensure Total Tank Safety. Request a Quote for Our Integrated Breather Valves Today.”
Everything You Need to Know About Valves with Inside Elements
Q1: What is the benefit of having the flame element “inside” the breather valve?
A1: This integrated design saves significant installation space on the tank top and reduces costs by combining two essential safety devices—a breather valve and a flame arrester—into a single unit.
Q2: Can the internal flame element be cleaned or replaced?
A2: Yes. The ZCBV-IZ is designed for easy disassembly, allowing the flame element to be removed, inspected, and cleaned to maintain optimal flow and safety performance.
Q3: Does the internal element increase the pressure drop across the valve?
A3: Our engineers have optimized the internal matrix of the corrugated filter element to ensure minimal resistance while providing maximum flame quenching capability.
Q4: Is this valve suitable for corrosive chemical storage?
A4: Absolutely. We offer “Overall 304” or 316L stainless steel versions that provide excellent resistance to aggressive chemical vapors and saline environments.
Q5: What flange standards are compatible with the ZCBV-IZ?
A5: We support all major international standards, including ANSI, DIN, JIS, and GB, ensuring a perfect fit for your existing tank infrastructure.